Vertiv
Vertiv PSI5-800RT120N 800VA 720W Line-Interactive UPS 2U Rack/Tower
Line-interactive UPS delivers 800 VA and 720 W with automatic voltage regulation and six NEMA 5-15R outlets in a 2U rack/tower form factor
- International Version120V
- Input Voltage Range75-146VAC
- Input Frequency55~65Hz (57~63Hz Battery to Normal comeback)
- Input ConnectionNEMA 5-15
- VA Rating800VA
- Watts720W
Option PSI5-800RT120N
- PSI5-1100MT120
- PSI5-1100RT120
- PSI5-1500MT120
- PSI5-1500RM1201U
- PSI5-1500RT120
- PSI5-2200RT120
- PSI5-3000RT120
- PSI5-5000RT208
- PSI5-750MT120
- PSI5-800RT120
- PSI5-800RT120N
גרסאות עם קו חוצה קיימות, אך אינן במלאי כאן.
- 800VA 720W capacity protects critical electronics during outages
- 0 minutes half-load runtime allows orderly shutdown
- 5 minutes full-load runtime safeguards high-demand equipment
- 2U rack/tower design fits diverse installation spaces
- 1372 joules surge rating shields connected devices from spikes
Ideal for edge deployments
The Vertiv PSI5-800RT120N is a line-interactive UPS rated at 800VA and 720W, built for 120V environments. It protects active PFC power supplies, conventional power supplies, networking gear, workstations and point-of-sale systems in media closets or small racks. Six NEMA 5-15R outlets and a rotating LCD give clear status in either rack or tower orientation.
Upgrade from basic surge strips
This unit adds automatic voltage regulation across a 75-146VAC input window and pure battery backup with 5.5 minutes at full load or 16 minutes at half load. The jump is worthwhile when equipment needs orderly shutdown time or when voltage sags and swells exceed what a strip can absorb. It is not suited for loads that exceed 720W or for installations requiring extended runtime beyond the internal battery.
Simple 2U rack or tower setup
The 2U convertible chassis mounts in standard racks or sits as a tower with the display rotated. A hot-swappable battery cartridge (PSI5-24VBATT) reaches 90% charge in four hours. The only common pitfall is forgetting to configure the output voltage (100/110/115/125VAC) to match the connected gear before powering on.
נקודות עיקריות
- 800VA 720W capacity protects critical electronics during outages
- 0 minutes half-load runtime allows orderly shutdown
- 5 minutes full-load runtime safeguards high-demand equipment
- 2U rack/tower design fits diverse installation spaces
- 1372 joules surge rating shields connected devices from spikes
מפרט טכני
| Brand | Liebert |
|---|---|
| Series | PSI5 |
| Model | PSI5-800RT120N |
| International Version | 120V |
| Input Voltage Range | 75-146VAC |
| Input Frequency | 55~65Hz (57~63Hz Battery to Normal comeback) |
| Input Connection | NEMA 5-15 |
| VA Rating | 800VA |
| Watts | 720W |
| Output Voltage | 120VAC (100/110/115/125VAC user-configurable) |
| Outlets | 6 |
| Outlet Type | 6 x NEMA 5-15R |
| Battery Type | Valve Regulated Lead Acid (VRLA) |
| Battery Run Time | Full Load: 5.5 min Half Load: 16.0 min |
| Battery Recharge Time | 4 hours to recover 90% |
| Battery Replaceable | PSI5-24VBATT |
| Approvals | UL 1778, c-UL-us Listed |
| Rackmountable | 2U Rack/Tower |
| Surge Energy Rating | 1372 Joules |
| Temperature | Operating Temperature: 32°-104°F (0°-40°C) Storage Temperature: 5°-120°F (-15° - 50°C) |
| Humidity | 20% to 90% non-condensing |
| Dimensions | 3.5" x 17.2" x 16.1" |
| Weight | 28.4 lbs. |
| Package Contents | with RDU120 Network Card |
| משקל משלוח | 18.60 kg |
| מידות האריזה | 1364 × 1364 × 1364 mm |
גרסאות נוספות של דגם זה
2 נוספים באותה הסדרה
אותה משפחה, זיכרון, קירור או תדר שונים — השווה לפני שתחליט.
Vertiv PSI5-1100RT120 UPS 1100VA 990W 120V 2U Rack/Tower
- 120V
- 75-146VAC
שאלות על הפריט הזה
What rack depth does the 2U rack/tower chassis require for mounting?
The unit is a 2U rack/tower convertible design; allow standard 2U vertical space and ensure the rack depth accommodates the chassis length with clearance for rear cable connections.
How do I configure the output voltage to match my equipment?
Use the front-panel LCD menu to select 100, 110, 115, 120 or 125 VAC before connecting loads; the default is 120 VAC and the setting is retained after power cycles.
Which replacement battery kit restores runtime when the internal cells age?
Order the PSI5-24VBATT kit; recharge takes four hours to reach 90 % capacity and typical half-load runtime is 16 minutes with fresh batteries.
גם במדף הזה
לקוחות השוו בין אלה
אותו מדף, אותה קופה — שמונה מטבעות קריפטו ונעילת שער ל-30 דקות.
ModMyMods MOD-0002 3/8" ID x 1/2" OD Clear PVC Tubing DIY Cooling
- Clear





