Prihvaćamo kriptovalute — tako kriptovalute koje posjedujete mogu kupiti pravi hardver.Plaćajte kriptovalutom, trošite je na pravi hardver. Besplatna osigurana dostava diljem svijeta iznad 399 $. Obični vanjski kartoni bez oznaka, otpremaju se iz Njemačke.Besplatna osigurana dostava iznad 399 $. Vaš je tečaj blokiran 30 minuta od otvaranja blagajne.Tečaj blokiran 30 minuta. Svaki je artikl zapečaćen, njegov serijski broj provjeren, i pokriven jamstvom od 24 mjeseca.Zapečaćen, jamstvo 24 mjeseca.

Praćeni artikli Prijava

Vertiv

Vertiv AS6A0NCUGNNXLKB 5 kVA UPS 4.5 kW 5 min runtime

SKU CH-378B-56XV6 MPN AS6A0NCUGNNXLKB

Online double-conversion UPS delivers 5 kVA and 4.5 kW with five minutes full-load runtime and scales to 20 kVA N+1

  • International Version208V
  • Input Voltage Range200/100, 208/120, 220/110, 230/115, 240/120 VAC
  • Input Frequency40 Hz to 70 Hz auto-sensing
  • Input Connection4-Wire (L-L-N-G)
  • VA Rating5 kVA
  • Watts4.5 kW
  • Scalable to 20 kVA N+1 redundancy for growing critical loads
  • Online double-conversion topology delivers continuous clean power to mission-critical equipment
  • Five minutes full-load runtime plus 15 minutes at half load from VRLA batteries
  • Wide 40–70 Hz auto-sensing input tolerates unstable generator or utility sources
  • Rack or tower form factor with LCD status display fits diverse installation spaces

Mission-critical 5 kVA UPS

The Vertiv Liebert AS6A0NCUGNNXLKB is an online double-conversion UPS rated at 5 kVA and 4.5 kW, designed for mission-critical equipment. It accepts split-phase input voltages from 200/100 to 240/120 VAC with auto-sensing frequency between 40 Hz and 70 Hz. The unit operates in rack or tower orientation and supports scaling to 20 kVA N+1 redundancy.

Environmental sensors and monitoring

Factory-installed temperature, leak detection and humidity sensors provide continuous environmental awareness alongside the LCD status display. Hard-wired 4-wire L-L-N-G connections secure both input and output wiring for single-phase operation. User-configurable output frequency defaults to 60 Hz with 50 Hz selectable.

Five-minute full-load runtime

Valve-regulated lead-acid batteries deliver 5 minutes of runtime at full load and 15 minutes at half load. Operating temperature range spans 32°F to 104°F with humidity tolerance up to 95% non-condensing. Physical footprint measures 38" x 17" x 34" and weighs 415 lbs, requiring adequate floor or rack capacity.

Istaknuto

  • Scalable to 20 kVA N+1 redundancy for growing critical loads
  • Online double-conversion topology delivers continuous clean power to mission-critical equipment
  • Five minutes full-load runtime plus 15 minutes at half load from VRLA batteries
  • Wide 40–70 Hz auto-sensing input tolerates unstable generator or utility sources
  • Rack or tower form factor with LCD status display fits diverse installation spaces

Specifikacije

BrandVertiv
SeriesLiebert
ModelAS6A0NCUGNNXLKB
International Version208V
Input Voltage Range200/100, 208/120, 220/110, 230/115, 240/120 VAC
Input Frequency40 Hz to 70 Hz auto-sensing
Input Connection4-Wire (L-L-N-G)
VA Rating5 kVA
Watts4.5 kW
Output Voltage200/100, 208/120, 220/110, 230/115, 240/120 VAC
Output Frequency60Hz default; 50/60Hz user-configurable
Battery TypeValve Regulated Lead Acid (VRLA)
Battery Run TimeFull Load: 5 mins.
Half Load: 15 mins.
TemperatureOperating temperature: 32°F - 104°F (0°C - 40°C)
Humidity0 - 95%, non-condensing
Dimensions38" x 17" x 34"
Weight415 lbs.
Težina pošiljke188.24 kg
Dimenzije pakiranja965 × 864 × 432 mm

Druge verzije ovog modela

još 5 u istoj seriji

Ista obitelj, različita memorija, hladnjak ili frekvencija — usporedite prije kupnje.

Pitanja o ovom artiklu

How often will the Valve Regulated Lead Acid batteries need replacement?

The internal VRLA cells are rated for a 5-minute full-load runtime and 15 minutes at half load; typical service life is three to five years before capacity drops below useful levels.

What limits continuous output before the unit derates or shuts down?

The 4.5 kW rating is the sustained ceiling; exceeding it triggers immediate overload protection, and the 40 °C maximum operating temperature is the thermal limit that forces derating if airflow is restricted.

How much heat and fan noise should I expect when this UPS runs 24/7 at full load?

At 4.5 kW the double-conversion modules dissipate roughly 15 % of rated power as heat, and the internal fans ramp to maintain the 40 °C internal limit, producing noticeable but data-centre-typical airflow noise.