Tripp Lite
Tripp Lite SM1500RMXL2UTAA 1500VA 1350W 2U UPS
Line-interactive 2U rack/tower UPS delivers 1500VA/1350W sine-wave output, corrects 83V–145V, and offers 4.9 min full-load runtime
- Input Voltage Range120V
- Input ConnectionNEMA 5-15P
- VA Rating1500 VA
- Watts1350 Watts
- Output Voltage120V
- Output Frequency60Hz
- 1500VA 1350W capacity supports critical rack equipment
- Line-interactive design corrects voltage from 83V to 145V without battery drain
- Pure sine wave output protects sensitive servers and network gear
- Hot-swappable battery module enables replacement without downtime
- TAA compliance qualifies unit for GSA schedule procurement
TAA-compliant 1500VA rack UPS for servers
The Tripp Lite SM1500RMXL2UTAA is a line-interactive uninterruptible power supply rated at 1500VA and 1350W. It delivers pure sine-wave output at 120V 60Hz through eight NEMA 5-15R outlets. The unit fits a 2U rack space and meets Federal Trade Agreements Act requirements for GSA Schedule procurement.
Input range 83V to 145V
The UPS corrects brownouts and overvoltages without using battery power across a 83V to 145V window. Voltages between 127V and 145V are reduced by 12 percent. Surge protection is rated at 570 joules. The NEMA 5-15P input plug connects to a standard 120V circuit.
Hot-swap VRLA batteries with SNMP card slot
Valve-regulated lead-acid batteries (replacement cartridge RBC93-2U) are user-replaceable without shutting down connected equipment. Runtime is 4.9 minutes at full load and 14 minutes at half load. Recharge from 10 to 90 percent takes less than 4.5 hours. Management interfaces include USB, DB9 serial, emergency power-off and an open slot for an optional SNMP or web card. Buyers needing longer runtime at full load or three-phase input cannot meet those needs with this model.
商品特色
- 1500VA 1350W capacity supports critical rack equipment
- Line-interactive design corrects voltage from 83V to 145V without battery drain
- Pure sine wave output protects sensitive servers and network gear
- Hot-swappable battery module enables replacement without downtime
- TAA compliance qualifies unit for GSA schedule procurement
商品規格
| Brand | TRIPP LITE |
|---|---|
| Model | SM1500RMXL2UTAA |
| Input Voltage Range | 120V |
| Input Connection | NEMA 5-15P |
| VA Rating | 1500 VA |
| Watts | 1350 Watts |
| Output Voltage | 120V |
| Output Frequency | 60Hz |
| Outlets | 8 |
| Outlet Type | 5-15R |
| Battery Type | Valve Regulated Lead Acid (VRLA) |
| Battery Run Time | Full load runtime (minutes) 4.9 min. Half load runtime (minutes) 14 min. |
| Battery Recharge Time | Less than 4.5 hours from 10% to 90% |
| Battery Replaceable | RBC93-2U |
| Alarms | Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
| Interface Port | USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
| Rackmountable | 2U |
| Surge Energy Rating | 570 joules |
| Protection | Input voltages between 127 and 145 are reduced by 12% |
| Features | Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases Tripp Lite SM1500RMXL2UTAA line interactive 2U rack/tower UPS with 1500VA / 1.5kVA / 1350W capacity and extended runtime options Line interactive UPS with Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages from 83 to 145V NEMA 5-15P input plug; 8 NEMA 5-15R output receptacles, Two independently switched output load banks Maintains uninterrupted operation of connected networking equipment during blackouts, surges, brownouts and overvoltages High 95% efficiency rating in line-power mode |
| Dimensions | 3.45" x 17.3" x 13.45" (H x W x D) |
| Weight | 46.5lbs |
| Package Contents | SM1500RMXL2UTAA TAA Compliant UPS System PowerAlert software with USB, Serial & EPO cabling 4 post installation kit Owner's manual |
| 出貨重量 | 24.38 kg |
| 包裝尺寸 | 605 × 518 × 224 mm |
商品問答
Should I pick the 1500 VA model or a lower-capacity unit for my rack?
Choose this 1500 VA / 1350 W unit when your connected load approaches 1.35 kW; it delivers 4.9 minutes at full load and 14 minutes at half load, while a smaller model would exhaust its battery sooner.
What does the 1350 W rating mean once the UPS is installed in my rack?
It is the maximum real power the inverter can supply continuously; at that load the internal VRLA batteries last 4.9 minutes, giving you time to shut down servers gracefully.
Which management interfaces are on the rear panel and what do they control?
USB, DB9 serial, EPO contact and an open slot for an SNMP/Web card provide local monitoring, graceful shutdown scripts, emergency power-off triggering and optional network management.
同類商品
顧客也比較過
同一分類,同一套結帳流程 — 支援八種加密貨幣,匯率鎖定 30 分鐘。
Thermal Grizzly TG-MP8-120-20-30-1R Minus Pad 8 chipset cooling 120x20x3.0mm
DOCTOR METAL 3x 120mm case fan pack white with controller
- Case Fan
- Case