Tripp Lite
Tripp Lite SUINT3000LCD2U UPS 3000VA 2.7kW 208V 10 Outlets 2U
Double-conversion UPS delivers 3000 VA / 2700 W at 208 V with 10 IEC outlets, hot-swappable batteries and USB, RS-232 plus SNMP slot in 2U rack form
- International Version208V
- Input ConnectionNEMA L6-20P
- VA Rating3000 VA
- Watts2700 Watts
- Output Voltage208V
- Output Frequency50 / 60 Hz
- Double-conversion online topology delivers clean 208 V power to critical loads
- 3000 VA and 2700 W capacity supports dense rack equipment
- Ten IEC outlets (eight C13, two C19) connect servers and networking gear
- Hot-swappable VRLA batteries replace without downtime in three hours to 90 %
- USB, RS-232, contact closure and SNMP card slot enable remote monitoring
Tripp Lite SmartOnline 3000VA 2U UPS
The Tripp Lite SUINT3000LCD2U is a double-conversion online UPS rated at 3000 VA and 2700 watts with a 208V output. It fits a 2U rack space and provides ten outlets, eight C13 and two C19, fed from a NEMA L6-20P input. The unit suits servers, network gear and critical loads that require continuous power conditioning.
Upgrade from line-interactive or standby units
Moving from a line-interactive or standby UPS is worth it when connected equipment cannot tolerate any transfer time or voltage distortion. The online topology regenerates a clean sine wave continuously, eliminating switchover delays and correcting sags, surges and frequency drift before they reach the load. Buyers who only need basic battery backup for non-critical devices will not benefit from the added cost and complexity.
Rack installation with hot-swappable batteries
The 2U chassis mounts in standard racks using included hardware; the NEMA L6-20P plug requires a matching 20 A branch circuit. Batteries are user-replaceable and hot-swappable, so runtime can be restored without powering down the load. Common issues include forgetting to seat the internal battery connectors after replacement and exceeding the 16 A input rating when the load approaches full capacity.
Puntos fuertes
- Double-conversion online topology delivers clean 208 V power to critical loads
- 3000 VA and 2700 W capacity supports dense rack equipment
- Ten IEC outlets (eight C13, two C19) connect servers and networking gear
- Hot-swappable VRLA batteries replace without downtime in three hours to 90 %
- USB, RS-232, contact closure and SNMP card slot enable remote monitoring
Especificaciones
| Brand | TRIPP LITE |
|---|---|
| Series | SmartOnline |
| Model | SUINT3000LCD2U |
| International Version | 208V |
| Input Connection | NEMA L6-20P |
| VA Rating | 3000 VA |
| Watts | 2700 Watts |
| Output Voltage | 208V |
| Output Frequency | 50 / 60 Hz |
| Outlets | 10 |
| Outlet Type | (8) C13; (2) C19 |
| Battery Type | Valve Regulated Lead Acid (VRLA) |
| Battery Run Time | Full Load : 3.8 min. (2700W) Half Load: 10.8 min. (1350W) |
| Battery Recharge Time | 3 hours recharge to 90% |
| Battery Replaceable | Hot-swappable, user replaceable batteries |
| Alarms | Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
| Interface Port | (1) Contact closure; (1) RS-232; (1) Slot for SNMP/Web interface; (1) USB |
| Rackmountable | Yes |
| Surge Energy Rating | 296 Joules |
| Temperature | Operating Temperature Range: 32° to 104°F (0° to 40°C) Storage Temperature Range: With battery: 32° to 104°F (0° to 40°C); without battery: -13° to 131°F (-25° to 55°C) |
| Humidity | 0-96% non-condensing |
| Dimensions | 3.41" x 17.33" x 23.82" |
| Weight | 61.29 lbs. |
| Package Contents | 3000VA 2700W 208/230V Double-Conversion UPS Detachable C19 to L6-20P 16A power cord, 6 ft. (1.8 m) USB cable DB9 cable (2) IEC 10A 6ft. output cables Rack-mounting hardware Tower support stands Safety instructions Quick start guide |
| Peso de envío | 30.94 kg |
| Dimensiones del paquete | 760 × 600 × 240 mm |
Preguntas sobre este artículo
What rack depth and clearance does the 2U chassis need to fit?
The unit occupies 2U of rack height and requires a standard 19-inch rack; allow front clearance for the LCD panel and rear access for the NEMA L6-20P inlet and ten outlets.
Which step is often missed when wiring the NEMA L6-20P input and the eight C13 plus two C19 outlets?
Connect the L6-20P plug to a 208 V 20 A branch circuit, then verify each C13 and C19 load cable is fully seated; the RS-232, USB and SNMP slot cables must also be attached before powering on.
When and how should the hot-swappable VRLA battery modules be replaced?
Replace modules when runtime drops below the 3.8-minute full-load or 10.8-minute half-load figures; slide out the old pack and insert the new one without shutting down the UPS.